1. The cyclone should be stable, with minimal impact from the reflux of cold and wet gas. It should be placed on the windward side of the building's minimum frequency wind direction.

2. Cooling towers should not be placed on heat sources. Exhaust gas and dust around the sewage outlet are unsuitable for placement in narrow, elongated areas between tall buildings.

3. Cooling towers should be arranged separately. When multiple arrangements are needed, Mr. Du, HVAC design expert, suggests that the distance between counter-flow towers should meet the following regulations:

①. For adjacent tower rows with major axes along the same straight line, the spacing should not be less than 4m.

②. For tower rows arranged in parallel but not along the same straight line, the spacing should not be less than 4 times the intake of the tower, and the ratio of row length to total width should not exceed 5:1.

4. The air intake side of a single-side intake tower should face the prevailing summer wind direction, while the air intake sides of double-sided intake towers should be parallel to the prevailing summer wind direction.

5. The distance between the air intake side of the cooling tower and the building should exceed twice the tower's air intake; in addition to ventilation requirements and pipeline construction locations, maintenance passages should also be provided around the cooling tower, with a passage spacing of not less than 1.0m.

6. The distance between the cooling tower and adjacent buildings facing the cooling tower windows should not be less than 3.0m. This not only satisfies the cooling tower's ventilation requirements but also considers the impact of noise and water leakage on the building.

00

7. For intermittent open cooling systems, the effective water collection capacity of the cooling tower base or sump should exceed the sum of the water consumption of wet cooling tower fillers and other components and the water capacity of the pipeline flowing in by gravity when the pump is stopped.

8. The cooling water sump should be placed as close to the cooling tower as possible.

9. Cooling towers should be placed under special circumstances; they should not be directly placed on the floor or roof.

10. When the cooling tower installation environment has high noise control requirements, the following measures can be taken:

①. Avoid placing the cooling tower in noise-sensitive areas.

②. Select low-noise or ultra-low-noise cooling towers.

③. Install vibration damping and noise reduction equipment at the inlet, outlet, and make-up water pipe.

④. Install a wind deflector on the cooling tower to direct the exhaust air away from the building.

⑤. Install sound insulation and sound absorption barriers on the building.

⑥. Install vibration isolation devices for the cooling tower base.

12

2023-04

Three cooling methods of closed cooling towers: countercurrent, crosscurrent, and mixed flow. What are their differences and characteristics?

Three cooling methods of closed cooling towers: countercurrent, crosscurrent, and mixed flow. What are their differences and characteristics?

12

2023-04

Precautions for using closed-circuit cooling towers

Precautions for using closed-circuit cooling towers I. Usage environment ★ Avoid areas with acidic exhaust gas, explosive dust, heavy coal smoke, and excessive water vapor: ★ When placed next to buildings, maintain a sufficient distance from the air inlet (0.5-3 meters, depending on the model) ★ When placed in a well-type enclosure, be wary of the recirculation of humid air causing heat dissipation failure. A draft device may be considered for special environments.

03

2023-01

Reasons for regular cleaning of cooling tower fillers (What are the benefits of cleaning cooling tower fillers on time)

What are the benefits of regular cleaning of cooling tower fillers? What are the reasons for regular cleaning of cooling tower fillers? How much do you know about it?

03

2023-01

Which company is better for cleaning cooling tower fillings (cooling tower manufacturers good at cleaning cooling tower fillings)

Which company is better for cleaning cooling tower fillers? Guangdong Teling Air Conditioning is engaged in cooling tower cleaning, cooling tower chemical cleaning, cooling tower cleaning agents, cooling tower cleaning powder, cooling tower cleaning liquid, cooling tower descaling, cooling tower descaling agents, cooling tower descaling powder, cooling tower descaling liquid, cooling tower chemical cleaning, and cooling tower chemical cleaning agents. Next, let's introduce some knowledge related to cooling tower filler cleaning.

03

2023-01

What are the roles of cooling tower components in cooling tower renovation?

The heat exchange capacity of a cooling tower is mainly determined by the air-water ratio. Traditional technologies are not very efficient and the effect is not obvious. If the cooling tower is retrofitted with Mali Liangji cooling tower accessories, the shaft power of the water turbine can be the same as the motor power. The structure, shape, specifications, and refrigeration principle of the cooling tower do not need to be changed.

03

2023-01

What are the precautions after installing a cooling tower gear reducer (cooling tower gear reducer installation and maintenance)?

What needs to be done after installing a Liangji cooling tower gearbox? Precautions after installing a Liangji cooling tower gearbox

03

2023-01

Correct Installation Methods for Cooling Towers (Cooling Tower Installation and Construction Manufacturers)

Cooling towers are a common type of cooling and heat dissipation equipment in water system central air conditioning systems. Common brands of cooling towers used in central air conditioning systems include: Marley, SPX, Ebara, Yimea, BAC, Liangji, Jinri, etc. Cooling towers are mainly open and closed cooling towers. The main difference between open and closed cooling towers is that the circulating water in open cooling towers cannot withstand pressure, while the circulating water in closed cooling towers can withstand pressure. We share a cooling tower installation and construction method for your technical reference.

Service Hotline:

E-mail:dykj1688@yeah.net

Address: Guangdong Province, Huizhou City, Boluo County, Longxi Town, Longyuan Avenue, Dongyan Technology Industrial Park

 

 

Follow us

Dongyan

Scan with your phone


Copyright © Guangdong Dongyan Cooling Equipment Co., Ltd. All rights reserved.

Business License

Power by:www.300.cn | SEO | Privacy Policy